K. Guller Insulation installs thermal and acoustic insulation on commercial HVAC duct systems — flexible duct wrap, internal duct liner, and rigid board — sized to meet IECC and ASHRAE 90.1 requirements. We also install listed fire-rated duct wrap on kitchen grease exhaust and ventilation ducts where a rated enclosure isn’t practical. Union Heat & Frost Insulators perform all work across Pennsylvania, New Jersey, and Delaware.

Which ducts need insulation, and to what R-value?

Under the IECC and ASHRAE 90.1, supply and return ducts generally require R-6 to R-12 depending on location — ducts outdoors or in unconditioned attics need the most, ducts in conditioned space may need none — and cooled ducts also need a vapor retarder to prevent condensation.

Duct location Typical requirement Notes
Exterior / rooftop R-8 to R-12 Weatherproof jacketing; vapor-sealed if cooled
Unconditioned attic or space R-6 to R-12 Highest exposure to condensation risk
Indirectly conditioned (plenums, shafts) R-1.9 to R-6 Per adopted code edition
Conditioned space Often exempt Liner may still be specified for acoustics
Duct location Typical requirement Notes
Exterior / rooftop R-8 to R-12 Weatherproof jacketing; vapor-sealed if cooled
Unconditioned attic or space R-6 to R-12 Highest exposure to condensation risk
Indirectly conditioned (plenums, shafts) R-1.9 to R-6 Per adopted code edition
Conditioned space Often exempt Liner may still be specified for acoustics

Exact values depend on the code edition adopted in your jurisdiction and the climate zone (most of our footprint is Zone 4A/5A). Our estimators price to the spec section — typically 23 07 13 (duct insulation) — and flag conflicts between drawings and code before they become RFIs.

Duct wrap, duct liner, or duct board...which do you need?

Many projects combine all three; the spec and the acoustic requirements decide. If the drawings are silent, we’ll recommend the assembly that meets code at the lowest installed cost — and put it in writing.

Do you install fire-rated grease duct wrap?

Yes. Where a Type I kitchen exhaust duct can’t be enclosed in a rated shaft, we install listed flexible enclosure systems (fire-rated duct wrap) tested to ASTM E2336, providing the code-required rating in as little as 1.5–3 inches of thickness. The same family of listed wraps covers ventilation and hazardous-exhaust ducts requiring an hourly rating. Every installation follows the specific listing — layers, overlaps, banding, and penetration details — and we document the system for the AHJ.

Why does condensation control matter on cooled ducts?

A cooled duct running through humid unconditioned space is a condensation machine: surface temperatures below the dew point mean sweating ducts, stained ceilings, wet insulation that no longer insulates, and mold complaints. The fix is the right thickness of insulation plus a continuous sealed vapor retarder — taped and mastic-sealed FSK facing with no gaps at hangers, joints, or damage points. This is craft-sensitive work, which is why apprenticeship-trained insulators matter more on cold systems than anywhere else.

Still have questions?

Our team is ready to help you with any inquires you my have.

FAQ

Got Questions? We’ve Got Answers

Find answers to common questions about our services, processes, and how we work with clients across various industries.

Typically R-6 to R-12 depending on duct location and the adopted code edition — exterior and attic ducts need the most, and ducts fully inside conditioned space are often exempt. Cooled ducts also require a sealed vapor retarder.

Duct wrap is installed on the outside of the duct for thermal performance and condensation control; duct liner is installed inside the duct and provides both insulation and sound absorption.

Sometimes. Return ducts in unconditioned spaces generally require insulation under the energy code; returns within conditioned space usually don’t, unless the spec calls for liner acoustically.

Usually a failed vapor retarder on a cooled duct — humid air reaches the cold metal, condenses, and soaks the insulation. Wet fiberglass loses its R-value and should be replaced, not dried in place.

KG Insulation installs duct wrap, liner, board, and fire-rated duct wrap on commercial projects across eastern PA, NJ, and DE from Lafayette Hill, PA. Call (610) 941-9394.